usp icon Over 50 Years of Expertise and Experience
usp icon Over 10,000 Items in Stock
usp icon Fast Delivery

LioN-P, IO-Link Master

€1,020.15*

piece
Article number: 0980 ESL 399-121-EEC
Manufacturer number: 934879072
EAN: 04001088147546
Brand: Belden
Minimum order quantity: 1
Product information
The LioN-P IO-Link Master is designed to facilitate efficient communication and control within industrial environments. Housed in a robust metal casing, this master unit supports multiprotocol operations, including PROFINET and EtherNet/IP, ensuring versatile integration into various systems. Measuring 60mm wide and capable of withstanding harsh conditions up to IP69K, it is ideal for use in demanding environments. It features 4 galvanically isolated digital input channels and 4 digital output channels, each capable of handling up to 2A. Additionally, it provides 8 IO-Link Master ports, supporting Class A and Class B devices, with comprehensive diagnostic and status indicators. The device supports multiple power connection options with M12 L-coded connectors, ensuring reliable and stable power supply. The LioN-P also boasts extended environmental conditions tolerance, operating efficiently in temperatures as low as -40°C.

Benefits of the LioN-P IO-Link Master include its multiprotocol support which ensures compatibility with various network standards, making it highly versatile. Its robust metal housing and IP69K rating provide excellent protection in harsh and rugged environments. The device's multiple IO-Link Master channels facilitate extensive device connectivity and control. Comprehensive diagnostic and status indicators aid in easy monitoring and troubleshooting.

The LioN-P IO-Link Master is perfect for various applications in industrial automation, including machinery control, sensor and actuator integration, and factory automation. Its flexibility, robust design, and high protection rating make it suitable for both standard and demanding industrial tasks, ensuring reliable operation and connectivity across multiple devices and networks.
Downloads
Specifications
Protocol (EtherNet/IP): EtherNet/IP
Pollution Degree: 3 acc. to EN 60664-1, VDE 0110-1
Permissible Humidity (Storage/Transport): 5 % ... 95 % (For UL applications max. 80 %)
Permissible Humidity (Operation): 5 % ... 95 % (For UL applications max. 80 %)
Perm. Conductor Length to Device: ≤ 20 m
Performance Class: RT (switch supports IRT)
Part Number (#1): 934879072
Parameter Storage (#1): Supported
PNO:
Overload Behavior: Auto off and on switching / Manual restart
Output Wiring: 2-wire
Potted:
Product Family: I/O Systems: Active - Standalone
Protocol (#4): PROFINET
Protective Circuit (#1): Electronicaly: Overload protection, short-circuit protection
Protective Circuit: Electronicaly: Overload protection, short-circuit protection
Protection Degree / IP Rating**: IP65, IP67, IP69K
Protection Degree / IP Rating Note: ** only if mounted and locked in combination with Hirschmann / Lumberg Automation connector.
Protection Class: III, IEC 61140, EN 61140, VDE 0140-1
Product Sub Family: LioN-P
Output Current per Module: max. 9 A
Output Current per Channel: max. 2 A (Pin 2) / max. 0.5 A (Pin 4)
Number of Connections (#3): 2
Nominal Voltage (#2): 24 V DC via US (module power supply)
Nominal Voltage (#1): 24 V DC via US (system power supply)
Nominal Voltage: Pin 4: 24 V DC via US (system power supply) / Pin 2: 24 V DC via Uaux (auxiliary power supply)
Nominal Current C/Q (Pin 4): max. 500 mA (via US)
Nominal Current 2L+/Uaux (Pin 2, B Ports): max. 2 A per port (via Uaux)
Nominal Current 1L+ (Pin 1): max. 500 mA (via US)
Nominal Current: typ. 3 mA
Netload Class: II
Mounting: 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts.
Number of Connections (#5): 2
ODVA:
O-Ring Material: FKM
Number of Ports (#1): 8x, X1 to X8
Number of Ports: 8x, X1 to X8
Number of IO-Link Master Channels: max. 8, configurable
Number of Digital Output Channels: max. 12, configurable
Number of Digital Input Channels: max. 12, configurable
Number of Connections (#6): 2
Module Supply Voltage (Range): 18 V DC to 30 V DC
Width (#1): 2.3622 in
Transmission Method (#3): 100 BASE-TX, with auto negotiation and auto crossing
Transmission Method: 100 BASE-TX, with auto negotiation and auto crossing
Topology Detection: LLDP, SNMP V1
System Power Supply Connection Note: *do not connect / disconnect under voltage!
Supported Network Protocols (Other) (#2): ARP, HTTP, Ping, SNMP V1, TCP/IP
Supported Network Protocols (Other) (#1): ACD, ARP, BootP, DHCP, HTTP, IGMP, Ping, TCP/IP
Transmission Rate (#3): Fast Ethernet (10/100 Mbit/s), Full Duplex
Transmission Rate (#5): Fast Ethernet (10/100 Mbit/s), Full Duplex
Width: 60 mm
Weight: 500 g
Vibration Resistance: 15 g / 5 -500 Hz
Uaux / FE: 500 V DC
US (System Supply Voltage) / FE: 500 V DC
UL-File: E230848
UL: cULus Listed, UL 61010-1
Shock Resistance: 50 g / 11ms
Shared Device: Supported
Sensor Type: PNP
Sensor Supply Voltage (Range): 18 V DC to 30 V DC
Sensor Supply Voltage (Nominal): 24 V DC (SELV/PELV)
Sensor Current Supply: max. 500 mA per port via 1L+
RoHS Compliant:
Reverse Polarity Protection (#2):
Reverse Polarity Protection (#1):
Reverse Polarity Protection:
Specification: V2.3X
Specification (#1): CIP V3.1x, EIP Adaption of CIP V1.1x
Supported COM Modes: 4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3)
Status Indicator (System Supply): LED green
Status Indicator (Sensor Supply): LED green
Status Indicator (Outputs): LED white or yellow per channel
Status Indicator (Inputs): LED white or yellow per channel
Status Indicator (IOL): LED green per channel
Status Indicator (Actuator Supply): LED green
Quick Connect (QC): Not supported
Module Supply Voltage (Nominal): 24 V DC (SELV/PELV)
Cycle Time / Requested Packet Interval (RPI): min. 1 ms
Connection (#3): M12, 5-poles, A-coded
Connection (#2): M12, 5-poles, A-coded
Connection (#11): M12 LAN, 4-poles, D-coded
Connection (#10): M12 LAN, 4-poles, D-coded
Conformance Class: C
China RoHS-Compliant:
Channel Type (#1): Type 1 acc. to IEC 61131-2
Connection (#9): M12, 5-poles, A-coded
Customer Specific Product:
Current Consumption (typ.): 180 mA (at 24 V DC)
Current Carrying Capacity of Connector (#2): max. 16 A
Current Carrying Capacity of Connector (#1): max. 16 A
Current Carrying Capacity of Connector: max. 16 A
Contact Bearer Material (#1): PA
Contact Base Material (#1): M12, D-coded, CuSn, Gold-plated | M12 Power, L-coded, CuNi, Gold-plated
Connection Types: Exclusive Owner, Input Only, Listen Only
Connection Sensor Supply Voltage: M12 Power, 5-poles, L-coded
Connection Module Supply Voltage: M12 Power, 5-poles, L-coded
Connection Actuator Supply Voltage: via Module Supply Connection
Channel Type: p-switching
CSA: Yes, via UL
CIP Msg Connection Limit: 6
Ambient Temperature (Operation)*: -40 °C to 70 °C
Air Pressure (Storage/Transport): 80 kPa … 106 kPa (up to 2000 m above sea level)
Air Pressure (Operation): 80 kPa … 106 kPa (up to 2000 m above sea level)
Addressing (#2): DCP
Addressing: BootP, DHCP, Rotary Address Switches
Address Switches Range (#1): 0 to 255 dec
Actuator Supply Voltage (Range): 18 V DC to 30 V DC
Actuator Supply Voltage (Nominal): 24 V DC (SELV/PELV)
Ambient Temperature (Storage/Transport): -40 °C to 85 °C
Ambient Temperature (operation), max: 70
CIP I/O Connection Limit: 3
CE:
Bus connection / FE: 2000 V DC
Ambient Temperature (storage/transport), min. (#1): Error
Ambient Temperature (storage/transport), min.: -25
Ambient Temperature (storage/transport), max. (#1): 85
Ambient Temperature (storage/transport), max.: Error
Ambient Temperature (operation), min. (#1): -20
Ambient Temperature (operation), min.: Error
Ambient Temperature (operation), max (#1): Error
Media Redundancy Protocol (MRP): Supported, MRP client
IO-Link:
Housing Plating: Nickel, matt
Housing Material: Metal, Zinc Die-cast
Housing Color: Grey Metallic
Height: 31 mm
Galvanically Isolated: Pin 4: No / Pin 2: Yes
Flammabilty Class: UL 94 (IEC 61010)
Fastening Torque (Power Connection): M12: 0.5 Nm
Fastening Torque (I/O Connection): M12: 0.5 Nm
Fastening Torque (Ground Connection (FE)): M4: 1 Nm
IO-Link Class A Ports: 4x, X1 to X4
IO-Link Class B Ports: 4x, X5 to X8
Mean Time To Failure (MTTF): 574 years. acc. to Telcordia SR-332 (2011) 20°C
Long Description (#1): LioN-P, IO-Link Master, Multiprotocol (PROFINET and EtherNet/IP), industrial metal housing, 60 mm, up to IP69K, 4 digital input and 4 digital output channels (2 A) with galvanic isolation and 8 IO-Link Master, 8 x M12 A-coded I/O connection, 5-poles, 2 x
Item Description: 0980 ESL 399-121-EEC
Input Wiring: 2-, 3-wire
Input Voltage Range "1" signal: 15 V DC ... 30 V DC
Input Voltage Range "0" signal: -0,3V DC ... 5 V DC
Included in Delivery: Attachable Labels: 15x, Sealing Caps: 5x M12
IO-Link Specification: V1.1.2
Fastening Torque (Fixing Screw): M4: 1 Nm
Fastening Torque (Bus Connection): M12: 0.5 Nm
Fast Startup (FSU): Supported, ≤ 2000 ms
Diagnostic Indicator (#2): LED red per port
Diagnostic Indicator (#1): LED red
Diagnostic Indicator: LED red
Diagnostic Idicator: LED red per port
Device Level Ring (DLR): Supported, beacon based
Depth (#1): 200 mm
Depth: 7.874 in
Cycle Time / Update Rate (#3): min. 1 ms
Cycle Time / Update Rate (#2): min. 8 ms for all channels at 32 Byte IN / OUT
Diagnostic Indicator (#3): LED red
Diagnostic Indicator (#4): LED red per port
Easy Device Replacement: Supported, based on LLDP
EN 61000-4-6 Conducted immunity: Criterion A; Test voltage 10 V
EN 61000-4-5 Surge Voltage: Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m
EN 61000-4-4 Fast Transients (Burst): Criterion B, 2 kV
EN 61000-4-3 Electromagnetic Field: Criterion A; Field intensity: 10 V/m
EN 61000-4-2 Electrostatic Discharge (ESD): Criterion B; 4 kV contact discharge, 8 kV air discharge
EN 55022 Radio Interference Properties: Class A
EMC Directive: 2014/30/EU
Dimensions (W x H x D): 60 mm x 31 mm x 200 mm
Unique No.: aut934879072