Product information
The LioN-P is an advanced IO-Link Master designed to meet the rigorous demands of industrial environments. Encased in a robust metal housing with protection ratings up to IP69K, this device supports multiprotocol operations (PROFINET and EtherNet/IP), making it highly versatile. The LioN-P features 4 digital inputs and 8 IO-Link master channels with M8 B-coded I/O connections and M12 Y-coded bus and power supply connections. With a nickel-plated, zinc die-cast construction, it offers excellent resistance to harsh conditions, ensuring longevity and reliability in various applications. The unit supports fast Ethernet communication with a transmission rate of up to 100 Mbit/s, auto-negotiation, and auto-crossing features. Its compact dimensions make it suitable for space-constrained installations, while the integrated diagnostic and status indicators ensure easy monitoring and maintenance. Applications range from industrial automation to smart manufacturing, where robust and reliable communication interfaces are critical.
Downloads
Specifications
Protocol (EtherNet/IP): | EtherNet/IP |
---|---|
Pollution Degree: | 3 acc. to EN 60664-1, VDE 0110-1 |
Permissible Humidity (Storage/Transport): | 5 % ... 95 % (For UL applications max. 80 %) |
Permissible Humidity (Operation): | 5 % ... 95 % (For UL applications max. 80 %) |
Perm. Conductor Length to Device: | ≤ 20 m |
Performance Class: | RT (switch supports IRT) |
Part Number (#1): | 934964002 |
Parameter Storage (#1): | Supported |
Overload Behavior: | Auto off and on switching / Manual restart |
Output Wiring: | 2-wire |
Potted: | |
Product Family: | I/O Systems: Active - Standalone |
Protocol (#4): | PROFINET |
Protective Circuit (#1): | Electronicaly: Overload protection, short-circuit protection |
Protective Circuit: | Electronicaly: Overload protection, short-circuit protection |
Protection Degree / IP Rating**: | IP65, IP67, IP69K |
Protection Degree / IP Rating Note: | ** only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. |
Protection Class: | III, IEC 61140, EN 61140, VDE 0140-1 |
Product Sub Family: | LioN-P |
Output Current per Module: | max. 6 A |
Output Current per Channel: | max. 0.5 A (Pin 4) |
Number of Connections (#3): | 2 |
Nominal Voltage (#2): | 24 V DC via US (module power supply) |
Nominal Voltage (#1): | 24 V DC via US (system power supply) |
Nominal Voltage: | 24 V DC via US (system power supply) |
Nominal Current C/Q (Pin 4): | max. 500 mA (via US) |
Nominal Current 2L+/Uaux (Pin 2, B Ports): | max. 4 A per module (via Uaux) |
Nominal Current 1L+ (Pin 1): | max. 500 mA (via US) |
Nominal Current: | typ. 3 mA |
Netload Class: | II |
Mounting: | 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. |
Number of Connections (#5): | 2 |
O-Ring Material: | FKM |
Number of Ports (#1): | 8x, X1 to X8 |
Number of Ports: | 8x, X1 to X8 |
Number of IO-Link Master Channels: | max. 8, configurable |
Number of Digital Output Channels: | max. 8, configurable |
Number of Digital Input Channels: | max. 12, configurable |
Number of Connections (#6): | 2 |
Module Supply Voltage (Range): | 18 V DC to 30 V DC |
Width (#1): | 1.1811 in |
Transmission Method (#3): | 100 BASE-TX, with auto negotiation and auto crossing |
Transmission Method: | 100 BASE-TX, with auto negotiation and auto crossing |
Topology Detection: | LLDP, SNMP V1 |
System Power Supply Connection Note: | *do not connect / disconnect under voltage! |
Supported Network Protocols (Other) (#2): | ARP, HTTP, Ping, SNMP V1, TCP/IP |
Supported Network Protocols (Other) (#1): | ACD, ARP, BootP, DHCP, HTTP, IGMP, Ping, TCP/IP |
Transmission Rate (#3): | Fast Ethernet (10/100 Mbit/s), Full Duplex |
Transmission Rate (#5): | Fast Ethernet (10/100 Mbit/s), Full Duplex |
Width: | 30 mm |
Weight: | 415 g |
Vibration Resistance: | 15 g / 5 -500 Hz |
Uaux / FE: | 500 V DC |
US (System Supply Voltage) / FE: | 500 V DC |
UL-File: | E230848 |
UL: | cULus Listed, UL 61010-1 |
Shock Resistance: | 50 g / 11ms |
Shared Device: | Supported |
Sensor Type: | PNP |
Sensor Supply Voltage (Range): | 18 V DC to 30 V DC |
Sensor Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Sensor Current Supply: | max. 500 mA per port via 1L+ |
RoHS Compliant: | |
Reverse Polarity Protection (#2): | |
Reverse Polarity Protection (#1): | |
Reverse Polarity Protection: | |
Specification: | V2.3X |
Specification (#1): | CIP V3.1x, EIP Adaption of CIP V1.1x |
Supported COM Modes: | 4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3) |
Status Indicator (System Supply): | LED green |
Status Indicator (Sensor Supply): | LED green |
Status Indicator (Outputs): | LED white or yellow per channel |
Status Indicator (Inputs): | LED white or yellow per channel |
Status Indicator (IOL): | LED green per channel |
Status Indicator (Actuator Supply): | LED green |
Quick Connect (QC): | Not supported |
Module Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Cycle Time / Requested Packet Interval (RPI): | min. 1 ms |
Connection (#3): | M8, 5-poles, B-coded |
Connection (#2): | M8, 5-poles, B-coded |
Connection (#11): | M12 Hybrid, 8-poles, Y-coded |
Connection (#10): | M12 Hybrid, 8-poles, Y-coded |
Conformance Class: | C |
China RoHS-Compliant: | |
Channel Type (#1): | Type 1 acc. to IEC 61131-2 |
Connection (#9): | M8, 5-poles, B-coded |
Customer Specific Product: | |
Current Consumption (typ.): | 180 mA (at 24 V DC) |
Current Carrying Capacity of Connector (#2): | max. 6 A |
Current Carrying Capacity of Connector (#1): | max. 6 A |
Current Carrying Capacity of Connector: | max. 6 A |
Contact Bearer Material (#1): | PA |
Contact Base Material (#1): | M12 Hybrid, Y-coded, CuSn, Gold-plated |
Connection Types: | Exclusive Owner, Input Only, Listen Only |
Connection Sensor Supply Voltage: | M12 Power, 5-poles, L-coded |
Connection Module Supply Voltage: | M12 Hybrid, 8-poles, Y-coded |
Connection Actuator Supply Voltage: | via Module Supply Connection |
Channel Type: | p-switching |
CSA: | Yes, via UL |
CIP Msg Connection Limit: | 6 |
Ambient Temperature (Operation)*: | -20 °C to 70 °C |
Air Pressure (Storage/Transport): | 80 kPa … 106 kPa (up to 2000 m above sea level) |
Air Pressure (Operation): | 80 kPa … 106 kPa (up to 2000 m above sea level) |
Addressing (#2): | DCP |
Addressing: | BootP, DHCP, Rotary Address Switches |
Address Switches Range (#1): | 0 to 255 dec |
Actuator Supply Voltage (Range): | 18 V DC to 30 V DC |
Actuator Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Ambient Temperature (Storage/Transport): | -25 °C to 85 °C |
Ambient Temperature (operation), max: | 70 |
CIP I/O Connection Limit: | 3 |
CE: | |
Bus connection / FE: | 2000 V DC |
Ambient Temperature (storage/transport), min. (#1): | Error |
Ambient Temperature (storage/transport), min.: | -25 |
Ambient Temperature (storage/transport), max. (#1): | 85 |
Ambient Temperature (storage/transport), max.: | Error |
Ambient Temperature (operation), min. (#1): | -20 |
Ambient Temperature (operation), min.: | Error |
Ambient Temperature (operation), max (#1): | Error |
Media Redundancy Protocol (MRP): | Supported, MRP client |
IO-Link: | |
Housing Plating: | Nickel, matt |
Housing Material: | Metal, Zinc Die-cast |
Housing Color: | Grey Metallic |
Height: | 43 mm |
Galvanically Isolated: | |
Flammabilty Class: | UL 94 (IEC 61010) |
Fastening Torque (Power Connection): | M12: 0.5 Nm |
Fastening Torque (I/O Connection): | M8: 0.3 Nm |
Fastening Torque (Ground Connection (FE)): | M4: 1 Nm |
IO-Link Class A Ports: | 4x, X1 to X4 |
IO-Link Class B Ports: | 4x, X5 to X8 |
Mean Time To Failure (MTTF): | 633 years. acc. to Telcordia SR-332 (2011) 20°C |
Long Description (#1): | LioN-P, IO-Link Master, Multiprotocol (PROFINET and EtherNet/IP), industrial metal housing, 30 mm, up to IP69K, 4 digital input and 8 IO-Link Master, 8 x M8 B-coded I/O connection, 5-poles, 2 x M12 Y-coded bus and power supply connection, 8-poles |
Item Description: | 0980 ESL 199-332 |
Input Wiring: | 2-, 3-wire |
Input Voltage Range "1" signal: | 15 V DC ... 30 V DC |
Input Voltage Range "0" signal: | -0,3V DC ... 5 V DC |
Included in Delivery: | Attachable Labels: 15x, Sealing Caps: 5x M12 |
IO-Link Specification: | V1.1.2 |
Fastening Torque (Fixing Screw): | M4: 1 Nm |
Fastening Torque (Bus Connection): | M12: 0.5 Nm |
Fast Startup (FSU): | Supported, ≤ 2000 ms |
Diagnostic Indicator (#2): | LED red per port |
Diagnostic Indicator (#1): | LED red |
Diagnostic Indicator: | LED red |
Diagnostic Idicator: | LED red per port |
Device Level Ring (DLR): | Supported, beacon based |
Depth (#1): | 183 mm |
Depth: | 7.2047 in |
Cycle Time / Update Rate (#3): | min. 1 ms |
Cycle Time / Update Rate (#2): | min. 8 ms for all channels at 32 Byte IN / OUT |
Diagnostic Indicator (#3): | LED red |
Diagnostic Indicator (#4): | LED red per port |
Easy Device Replacement: | Supported, based on LLDP |
EN 61000-4-6 Conducted immunity: | Criterion A; Test voltage 10 V |
EN 61000-4-5 Surge Voltage: | Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m |
EN 61000-4-4 Fast Transients (Burst): | Criterion B, 2 kV |
EN 61000-4-3 Electromagnetic Field: | Criterion A; Field intensity: 10 V/m |
EN 61000-4-2 Electrostatic Discharge (ESD): | Criterion B; 4 kV contact discharge, 8 kV air discharge |
EN 55022 Radio Interference Properties: | Class A |
EMC Directive: | 2014/30/EU |
Dimensions (W x H x D): | 30 mm x 43 mm x 183 mm |
Unique No.: | aut934964002 |