Product information
The LioN-P, IO-Link I/O Hub is designed for robust industrial environments, featuring a 60 mm industrial metal housing and protection up to IP69K. It offers 10 digital input and 6 digital output channels, each with a capacity of 0.5 A and galvanic isolation. The hub includes 8 x M12 A-coded I/O connections (5-poles) and 1x M12 A-coded IO-Link Class B connection (5-poles). The hub supports PX0 (Preconfigured Parameter Settings - Plug and Produce device exchange), facilitating easy and quick device swapping. The unit is compatible with IO-Link protocol, and offers LED indicators for system supply, sensor, actuator supply, and diagnostics. Its compact design ensures reliable operation in a wide range of temperatures and environmental conditions.
Downloads
Specifications
Actuator Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
---|---|
Actuator Supply Voltage (Range): | 18 V DC to 30 V DC |
Air Pressure (Operation): | 80 kPa … 106 kPa (up to 2000 m above sea level) |
Air Pressure (Storage/Transport): | 80 kPa … 106 kPa (up to 2000 m above sea level) |
Ambient Temperature (Operation)*: | -20 °C to 70 °C |
Ambient Temperature (Storage/Transport): | -25 °C to 85 °C |
Ambient Temperature (operation), max: | 70.0 |
Ambient Temperature (operation), max (#1): | Error |
Ambient Temperature (operation), min.: | Error |
Ambient Temperature (operation), min. (#1): | -20.0 |
Ambient Temperature (storage/transport), max.: | Error |
Ambient Temperature (storage/transport), max. (#1): | 85.0 |
Ambient Temperature (storage/transport), min.: | -25.0 |
Ambient Temperature (storage/transport), min. (#1): | Error |
Bus connection / FE: | 500 V DC |
CE: | |
CSA: | Yes, via UL |
Channel Type: | p-switching |
Channel Type (#1): | Type 3 acc. to IEC 61131-2 |
China RoHS-Compliant: | |
Configuration: | IODD, Process Data |
Connection (#2): | M12, 5-poles, A-coded |
Connection (#3): | M12, 5-poles, A-coded |
Connection (#4): | M12, 5-poles, A-coded |
Connection Actuator Supply Voltage: | via Module Supply Connection |
Connection Module Supply Voltage: | M12, 5-poles, A-coded |
Connection Sensor Supply Voltage: | via Module Supply Connection |
Contact Base Material (#1): | M12, A-coded, CuSn, Gold-plated |
Contact Bearer Material (#1): | PA |
Current Carrying Capacity of Connector: | max. 4 A |
Current Carrying Capacity of Connector (#1): | max. 4 A |
Current Carrying Capacity of Connector (#2): | max. 4 A |
Current Consumption (typ.): | 80 mA (at 24 V DC) |
Customer Specific Product: | |
Cycle Time / Update Rate (#1): | min. 1 ms |
Depth: | 6.2598 in |
Depth (#1): | 159 mm |
Diagnostic Idicator: | LED red per channel |
Diagnostic Indicator: | LED red |
Diagnostic Indicator (#1): | LED red |
Diagnostic Indicator (#3): | LED red |
Diagnostic Indicator (#4): | LED red per port |
Dimensions (W x H x D): | 60 mm x 31 mm x 159 mm |
EMC Directive: | 2014/30/EU |
EN 55022 Radio Interference Properties: | Class A |
EN 61000-4-2 Electrostatic Discharge (ESD): | Criterion B; 4 kV contact discharge, 8 kV air discharge |
EN 61000-4-3 Electromagnetic Field: | Criterion A; Field intensity: 10 V/m |
EN 61000-4-4 Fast Transients (Burst): | Criterion B, 2 kV |
EN 61000-4-5 Surge Voltage: | Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m |
EN 61000-4-6 Conducted immunity: | Criterion A; Test voltage 10 V |
Fastening Torque (Bus Connection): | M12: 0.5 Nm |
Fastening Torque (Fixing Screw): | M4: 1 Nm |
Fastening Torque (Ground Connection (FE)): | M4: 1 Nm |
Fastening Torque (I/O Connection): | M12: 0.5 Nm |
Fastening Torque (Power Connection): | M12: 0.5 Nm |
Flammabilty Class: | UL 94 (IEC 61010) |
Frame Type: | Type_2_V |
Galvanically Isolated: | |
Height: | 31 mm |
Housing Color: | Grey Metallic |
Housing Material: | Metal, Zinc Die-cast |
Housing Plating: | Nickel, matt |
IO-Link: | |
IO-Link Class: | Class B |
Input Filter Time: | 0 to 3 ms, configurable |
Input Voltage Range "0" signal: | -3 V DC …+5 V DC |
Input Voltage Range "1" signal: | 11 V DC … 30 V DC |
Input Wiring: | 2-, 3-, 4-wire |
Item Description: | 0960 IOL 385-001-PX0 |
Long Description (#1): | LioN-P, IO-Link I/O Hub, IO-Link, industrial metal housing, 60 mm, up to IP69K, 10 digital input and 6 digital output channels (0.5 A) with galvanic isolation, 8 x M12 A-coded I/O connection, 5-poles, 1x M12 A-coded IO-Link Class B connection, 5-poles, |
Mean Time To Failure (MTTF): | 1781 years. acc. to Telcordia SR-332 (2011) 20°C |
Module Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Module Supply Voltage (Range): | 18 V DC to 30 V DC |
Mounting: | 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. |
Nominal Current: | typ. 5 mA |
Nominal Voltage: | 24 V DC via Uaux (supplied by 2L+ of IO-Link Master) |
Nominal Voltage (#2): | 24 V DC via US (module power supply) |
Number of Connections (#6): | 1 |
Number of Connections (#9): | 1 |
Number of Digital Input Channels: | max. 10, fixed |
Number of Digital Output Channels: | max. 6, fixed |
Number of Ports: | 3x, X6 to X8 |
Number of Ports (#1): | 5x, X1 to X5 |
O-Ring Material: | FKM |
Output Current per Channel: | max. 0,5 A |
Output Current per Module: | Consider 2L+ limitation of connected IO-Link Master |
Output Wiring: | 2-, 3-wire |
Overload Behavior: | Auto off and on switching / Manual restart |
Parameter Storage: | Supported |
Part Number (#1): | 935001052 |
Permissible Humidity (Operation): | 5 % ... 95 % (For UL applications max. 80 %) |
Permissible Humidity (Storage/Transport): | 5 % ... 95 % (For UL applications max. 80 %) |
Pollution Degree: | 3 acc. to EN 60664-1, VDE 0110-1 |
Potted: | |
Process Data Length: | 4 Bytes Input Data, 4 Bytes Output Data |
Product Family: | I/O Systems: Active - Standalone |
Product Sub Family: | LioN-P |
Protection Class: | III, IEC 61140, EN 61140, VDE 0140-1 |
Protection Degree / IP Rating**: | IP65, IP67, IP69K |
Protection Degree / IP Rating Note: | ** only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. |
Protective Circuit: | Electronicaly: Overload protection, short-circuit protection |
Protective Circuit (#1): | Electronicaly: Overload protection, short-circuit protection |
Protocol: | IO-Link |
Reverse Polarity Protection: | |
Reverse Polarity Protection (#1): | |
Reverse Polarity Protection (#2): | |
RoHS Compliant: | |
Sensor Current Supply: | max. 700 mA per module (Consider 1L+ limitation of connected IO-Link Master) |
Sensor Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Sensor Supply Voltage (Range): | 18 V DC to 30 V DC |
Sensor Type: | PNP |
Shock Resistance: | 50 g / 11ms |
Specification (#4): | V1.1.2 |
Status Indicator (Actuator Supply): | LED green |
Status Indicator (Inputs): | LED white or yellow per channel |
Status Indicator (Outputs): | LED white or yellow per channel |
Status Indicator (Sensor Supply): | LED green |
Status Indicator (System Supply): | LED green |
System Power Supply Connection Note: | *do not connect / disconnect under voltage! |
Transmission Rate / COM Mode: | COM 3 (230.4 kbps) |
UL: | cULus Listed, UL 61010-1 |
UL-File: | E230848 |
US (System Supply Voltage) / FE: | 500 V DC |
Uaux / FE: | 500 V DC |
Vibration Resistance: | 15 g / 5 -500 Hz |
Weight: | 390 g |
Width: | 60 mm |
Width (#1): | 2.3622 in |
uniek_nr: | aut935001052 |