Product information
The LioN-P, IO-Link Master by Belden is designed for industrial environments, providing multiprotocol support for PROFINET and EtherNet/IP. Encased in a durable industrial metal housing, it measures 30 mm in width and is sealed up to IP69K, ensuring resistance to dust and high-pressure water. The unit offers versatile connectivity with 4 digital inputs and 8 IO-Link Masters, supported by 8 x M12 A-coded I/O connections. Additionally, it features 2 x M12 D-coded bus connections and 2 x M12 L-coded power supply connections, ensuring reliable performance in harsh conditions. The device enables easy integration into existing networks, supporting transmission rates of Fast Ethernet and robust communication protocols. Its rugged construction, including a sealed metal housing and gold-plated contacts, ensures long-term reliability even in the most challenging environments.
Downloads
Specifications
Actuator Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
---|---|
Actuator Supply Voltage (Range): | 18 V DC to 30 V DC |
Address Switches Range (#1): | 0 to 255 dec |
Addressing: | BootP, DHCP, Rotary Address Switches |
Addressing (#2): | DCP |
Air Pressure (Operation): | 80 kPa … 106 kPa (up to 2000 m above sea level) |
Air Pressure (Storage/Transport): | 80 kPa … 106 kPa (up to 2000 m above sea level) |
Ambient Temperature (Operation)*: | -20 °C to 70 °C |
Ambient Temperature (Storage/Transport): | -25 °C to 85 °C |
Ambient Temperature (operation), max: | 70 |
Ambient Temperature (operation), max (#1): | Error |
Ambient Temperature (operation), min.: | Error |
Ambient Temperature (operation), min. (#1): | -20 |
Ambient Temperature (storage/transport), max.: | Error |
Ambient Temperature (storage/transport), max. (#1): | 85 |
Ambient Temperature (storage/transport), min.: | -25 |
Ambient Temperature (storage/transport), min. (#1): | Error |
Bus connection / FE: | 2000 V DC |
CE: | |
CIP I/O Connection Limit: | 3 |
CIP Msg Connection Limit: | 6 |
CSA: | Yes, via UL |
Channel Type: | p-switching |
Channel Type (#1): | Type 1 acc. to IEC 61131-2 |
China RoHS-Compliant: | |
Conformance Class: | C |
Connection (#2): | M12, 5-poles, A-coded |
Connection (#3): | M12, 5-poles, A-coded |
Connection (#9): | M12, 5-poles, A-coded |
Connection (#10): | M12 LAN, 4-poles, D-coded |
Connection (#11): | M12 LAN, 4-poles, D-coded |
Connection Actuator Supply Voltage: | via Module Supply Connection |
Connection Module Supply Voltage: | M12 Power, 5-poles, L-coded |
Connection Sensor Supply Voltage: | M12 Power, 5-poles, L-coded |
Connection Types: | Exclusive Owner, Input Only, Listen Only |
Contact Base Material (#1): | M12, D-coded, CuSn, Gold-plated | M12 Power, L-coded, CuNi, Gold-plated |
Contact Bearer Material (#1): | PA |
Current Carrying Capacity of Connector: | max. 16 A |
Current Carrying Capacity of Connector (#1): | max. 16 A |
Current Carrying Capacity of Connector (#2): | max. 16 A |
Current Consumption (typ.): | 180 mA (at 24 V DC) |
Customer Specific Product: | |
Cycle Time / Requested Packet Interval (RPI): | min. 1 ms |
Cycle Time / Update Rate (#2): | min. 8 ms for all channels at 32 Byte IN / OUT |
Cycle Time / Update Rate (#3): | min. 1 ms |
Depth: | 8.8583 in |
Depth (#1): | 225 mm |
Device Level Ring (DLR): | Supported, beacon based |
Diagnostic Idicator: | LED red per port |
Diagnostic Indicator: | LED red |
Diagnostic Indicator (#1): | LED red |
Diagnostic Indicator (#2): | LED red per port |
Diagnostic Indicator (#3): | LED red |
Diagnostic Indicator (#4): | LED red per port |
Dimensions (W x H x D): | 30 mm x 43 mm x 225 mm |
EMC Directive: | 2014/30/EU |
EN 55022 Radio Interference Properties: | Class A |
EN 61000-4-2 Electrostatic Discharge (ESD): | Criterion B; 4 kV contact discharge, 8 kV air discharge |
EN 61000-4-3 Electromagnetic Field: | Criterion A; Field intensity: 10 V/m |
EN 61000-4-4 Fast Transients (Burst): | Criterion B, 2 kV |
EN 61000-4-5 Surge Voltage: | Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m |
EN 61000-4-6 Conducted immunity: | Criterion A; Test voltage 10 V |
Easy Device Replacement: | Supported, based on LLDP |
Fast Startup (FSU): | Supported, ≤ 2000 ms |
Fastening Torque (Bus Connection): | M12: 0.5 Nm |
Fastening Torque (Fixing Screw): | M4: 1 Nm |
Fastening Torque (Ground Connection (FE)): | M4: 1 Nm |
Fastening Torque (I/O Connection): | M12: 0.5 Nm |
Fastening Torque (Power Connection): | M12: 0.5 Nm |
Flammabilty Class: | UL 94 (IEC 61010) |
Galvanically Isolated: | |
Height: | 43 mm |
Housing Color: | Grey Metallic |
Housing Material: | Metal, Zinc Die-cast |
Housing Plating: | Nickel, matt |
IO-Link: | |
IO-Link Class A Ports: | 4x, X1 to X4 |
IO-Link Class B Ports: | 4x, X5 to X8 |
IO-Link Specification: | V1.1.2 |
Included in Delivery: | Attachable Labels: 15x, Sealing Caps: 5x M12 |
Input Voltage Range "0" signal: | -0,3V DC ... 5 V DC |
Input Voltage Range "1" signal: | 15 V DC ... 30 V DC |
Input Wiring: | 2-, 3-wire |
Item Description: | 0980 ESL 199-121 |
Long Description (#1): | LioN-P, IO-Link Master, Multiprotocol (PROFINET and EtherNet/IP), industrial metal housing, 30 mm, up to IP69K, 4 digital input and 8 IO-Link Master, 8 x M12 A-coded I/O connection, 5-poles, 2 x M12 D-coded bus connection, 4-poles, 2 x M12 L-coded power |
Mean Time To Failure (MTTF): | 604 years. acc. to Telcordia SR-332 (2011) 20°C |
Media Redundancy Protocol (MRP): | Supported, MRP client |
Module Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Module Supply Voltage (Range): | 18 V DC to 30 V DC |
Mounting: | 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts. |
Netload Class: | II |
Nominal Current: | typ. 3 mA |
Nominal Current 1L+ (Pin 1): | max. 500 mA (via US) |
Nominal Current 2L+/Uaux (Pin 2, B Ports): | max. 4 A per module (via Uaux) |
Nominal Current C/Q (Pin 4): | max. 500 mA (via US) |
Nominal Voltage: | 24 V DC via US (system power supply) |
Nominal Voltage (#1): | 24 V DC via US (system power supply) |
Nominal Voltage (#2): | 24 V DC via US (module power supply) |
Number of Connections (#3): | 2 |
Number of Connections (#5): | 2 |
Number of Connections (#6): | 2 |
Number of Digital Input Channels: | max. 12, configurable |
Number of Digital Output Channels: | max. 8, configurable |
Number of IO-Link Master Channels: | max. 8, configurable |
Number of Ports: | 8x, X1 to X8 |
Number of Ports (#1): | 8x, X1 to X8 |
O-Ring Material: | FKM |
ODVA: | |
Output Current per Channel: | max. 0.5 A (Pin 4) |
Output Current per Module: | max. 9 A |
Output Wiring: | 2-wire |
Overload Behavior: | Auto off and on switching / Manual restart |
PNO: | |
Parameter Storage (#1): | Supported |
Part Number (#1): | 934964004 |
Performance Class: | RT (switch supports IRT) |
Perm. Conductor Length to Device: | ≤ 20 m |
Permissible Humidity (Operation): | 5 % ... 95 % (For UL applications max. 80 %) |
Permissible Humidity (Storage/Transport): | 5 % ... 95 % (For UL applications max. 80 %) |
Pollution Degree: | 3 acc. to EN 60664-1, VDE 0110-1 |
Potted: | |
Product Family: | I/O Systems: Active - Standalone |
Product Sub Family: | LioN-P |
Protection Class: | III, IEC 61140, EN 61140, VDE 0140-1 |
Protection Degree / IP Rating**: | IP65, IP67, IP69K |
Protection Degree / IP Rating Note: | ** only if mounted and locked in combination with Hirschmann / Lumberg Automation connector. |
Protective Circuit: | Electronicaly: Overload protection, short-circuit protection |
Protective Circuit (#1): | Electronicaly: Overload protection, short-circuit protection |
Protocol (#4): | PROFINET |
Protocol (EtherNet/IP): | EtherNet/IP |
Quick Connect (QC): | Not supported |
Reverse Polarity Protection: | |
Reverse Polarity Protection (#1): | |
Reverse Polarity Protection (#2): | |
RoHS Compliant: | |
Sensor Current Supply: | max. 500 mA per port via 1L+ |
Sensor Supply Voltage (Nominal): | 24 V DC (SELV/PELV) |
Sensor Supply Voltage (Range): | 18 V DC to 30 V DC |
Sensor Type: | PNP |
Shared Device: | Supported |
Shock Resistance: | 50 g / 11ms |
Specification: | V2.3X |
Specification (#1): | CIP V3.1x, EIP Adaption of CIP V1.1x |
Status Indicator (Actuator Supply): | LED green |
Status Indicator (IOL): | LED green per channel |
Status Indicator (Inputs): | LED white or yellow per channel |
Status Indicator (Outputs): | LED white or yellow per channel |
Status Indicator (Sensor Supply): | LED green |
Status Indicator (System Supply): | LED green |
Supported COM Modes: | 4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3) |
Supported Network Protocols (Other) (#1): | ACD, ARP, BootP, DHCP, HTTP, IGMP, Ping, TCP/IP |
Supported Network Protocols (Other) (#2): | ARP, HTTP, Ping, SNMP V1, TCP/IP |
System Power Supply Connection Note: | *do not connect / disconnect under voltage! |
Topology Detection: | LLDP, SNMP V1 |
Transmission Method: | 100 BASE-TX, with auto negotiation and auto crossing |
Transmission Method (#3): | 100 BASE-TX, with auto negotiation and auto crossing |
Transmission Rate (#3): | Fast Ethernet (10/100 Mbit/s), Full Duplex |
Transmission Rate (#5): | Fast Ethernet (10/100 Mbit/s), Full Duplex |
UL: | cULus Listed, UL 61010-1 |
UL-File: | E230848 |
US (System Supply Voltage) / FE: | 500 V DC |
Uaux / FE: | 500 V DC |
Vibration Resistance: | 15 g / 5 -500 Hz |
Weight: | 480 g |
Width: | 30 mm |
Width (#1): | 1.1811 in |
uniek_nr: | aut934964004 |